Total cooling / heating output 100 W

Model No.

Packs of3384.540page

Material

Sheet steel_
_
Stainless steel__

Colour

RAL 7035_
_

Total cooling output 50Hz L35 L35 to DIN 14511 kW

_1.5_

Total cooling output 50/60 Hz L35 L35 kW

_1.5 / 1.65_

Total cooling output 50/60 Hz L35 L35 W

_1.15 / 1.3_

Rated operating voltage V , ~ , Hz

_400,2~ , 50/60_

Width mm

_597_

Height mm

_417_

Depth mm

_475_

Rated current max. A

_2.5 / 2.9_

Start- up current A

_8.7 / 7.6_

Pre - fuse A

___

Transformer circuit-breaker A

_6.3...10_

Motor circuit-breaker A

___

Power consumption p 50/60 Hz L35 L35 kW

_0.67 / 0.76_

Power consumption p 50/60 Hz L35 L50 kW

_0.79 / 0.93_

Operating temperature range

_+10 'C ...+55 'C_

Setting range

_+20 'C ...+55 'C_

Energy efficiency ratio (EER) 50 Hz L35 L35 to DIN EN 14511

_2.24_

Refrigerant g

_R134a , 700_

Permissible operating pressure (p.max) bar

_28_

Air throughput of fans (unimpeded air flow) , internal circuit/external circuit m/h

_491 / 1600_

Wight kg

_47.0_