Total cooling / heating output 100 W

Model No.

Packs of3385.510page

Material

Sheet steel_
_
Stainless steel__

Colour

RAL 7035_
_

Total cooling output 50Hz L35 L35 to DIN 14511 kW

_2_

Total cooling output 50/60 Hz L35 L35 kW

_2 / 2.14_

Total cooling output 50/60 Hz L35 L35 W

_1.41 / 1.51_

Rated operating voltage V , ~ , Hz

_115,1~ , 50/60_

Width mm

_597_

Height mm

_417_

Depth mm

_475_

Rated current max. A

_13.3 / 13.5_

Start- up current A

_42.2 / 31.1_

Pre - fuse A

___

Transformer circuit-breaker A

_14...20_

Motor circuit-breaker A

___

Power consumption p 50/60 Hz L35 L35 kW

_0.95 / 1.17_

Power consumption p 50/60 Hz L35 L50 kW

_1.07 / 1.24_

Operating temperature range

_+10 'C ...+55 'C_

Setting range

_+20 'C ...+55 'C_

Energy efficiency ratio (EER) 50 Hz L35 L35 to DIN EN 14511

_2.09_

Refrigerant g

_R134a , 900_

Permissible operating pressure (p.max) bar

_28_

Air throughput of fans (unimpeded air flow) , internal circuit/external circuit m/h

_470 / 1760_

Wight kg

_48.0_